Multi function Meter 3400 is a latest product in the SANDS Energy Management Solutions. For any Industry irrespective of their domain, the need of the hour is Energy Management System. One has to know what is the Energy that each one of the various departments consume daily/montly. To do this, we dont need a full blown Energy meter rather a cheap but feature rich Multifunction meter should suffice. MFM 3400 is one such meter that measures all the necessary electrical parameters for energy management system like Power, Power factor, Energy Import, Energy Export etc at 0.5S accuracy. Using Industry standard Modbus RTU protocol, any DCU can collect the parameters list from the MFM 3400 through RS485 interface

Features

Metering

  • Voltage VR, VY, VB, Total Voltage
  • Current IR, IY, IB, Total Current
  • Active Power R/Y/B and Total
  • Apparent Power R/Y/B and Total
  • Reactive Power R/Y/B and Total
  • Power Factor R/Y/B and Total
  • Frequency
  • Active Energy Import & Export
  • Reactive Energy Import & Export
  • Apparent Energy

Display

  • 56” 3 rows 4- digit 7-segment display Red lit
  • Status LEDs

Communication

  • Isolated RS485 with Industry standard Modbus-RTU Protocol

User Programmable Features

  • PT / CT Ratio
  • Modbus Slave Address (0-255)
  • Communication settings – Baud rate, Parity, Stop bits

Applications

  • Energy Management Systems
  • Metering for Industries and Utilities
  • Panel Metering of Distribution feeders, Generators, Transformers and Motors

Technical Specifications

Ratings
Voltage Inputs (Each channel)
Voltage range 60V – 300V (Ph-N)
Frequency Range 50+5%
Burden 0.2VA at 240V AC
Current Inputs (Each Channel)
Current range 10mA to 6A
Starting Current 0.1% of Full scale
Burden 0.1 VA at 5A AC
Accuracy Class 0.5S
Parameter Storage
Non-Volatile EEPROM (for Energy storage)
Display Page Selection
By set of keys provided in front panel
Communication
RS485 (Standard) Modbus-RTU Protocol, 2 Wire, Supports 4800 Baud rate (default)
Auxiliary Supply
Operating Range 90 – 270V AC, 50 / 60 Hz
110 – 300V DC
Burden <5VA at 240V AC
Operating Environment
Operating Temperature -10  C to +55  C
Storage Temperature -25  C to +75  C
Relative Humidity 5% to 9% non-condensing
Case and Dimension
Enclosure ABS
Dimension 96 x 96 x 65 mm
Type Tests
Measurement Standard IEC 62053-22, IS 14697
 

EMI/EMC Standard

IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
Safety Standard IEC 61010-1
Environmental Standard IEC 60068-2